Source: City of Greenville
According to Buddy Skinner, City of Greenville Assistant Building Codes Administrator, 25 percent of all electrical inspections on single family residential projects fail. Below is a list of the top reasons for inspection failures:
- Receptacle outlets should be located so that one can be reached within 6-feet measured along the wall surface in either direction. Outlets should also be located on any wall space 2-feet or larger. (2012 International Residential Code E3901.2)
- Receptacle outlets on kitchen counters should be located so that one can be reached within 2-feet measured along the wall surface in either direction. Outlets need to be installed above any kitchen counter 12-inches or wider. (2012 IRC E3901.4)
- Seal all drilled or notched holes in top and bottom plates with an approved material. (2012 IRC R302.11)
- Any neutral conductors (white in color) used as a phase conductor for a 220-volt circuit should be marked with black tape. This is commonly seen on conductors feeding a water heater or mechanical unit. (2012 IRC E33407.1 and E3407.2)
- Receptacles cannot be installed within or directly over a bathtub or shower stall. (2012 IRC E4002.11)
- No light fixture or fan can have suspended parts within 3-feet horizontally or 8-feet vertically from the top of the bathtub rim or shower stall threshold. (2012 IRC E4003.11)
- Watch the number of conductors that are installed in electrical boxes. A standard 20-cubic inch nail-on electrical box can have two romex wires and a device. A 22-cubic inch nail-on electrical box can have three romex wires and a device (2012 IRC E3905.12)
- Provide at least 6-inches of wire for device connection at each electrical box. (2012 IRC E3406.11.3)
- Arc-fault circuit protection is required for all circuits within a dwelling except for those required to be ground-fault protected. Wiring that supplies only smoke detectors do not have to be arc-fault protected. (2012 IRC E3902.12)
- In new dwelling units that have attached garages or fuel-fired appliances, carbon monoxide alarms must be installed outside each separate sleeping area near the bedroom or bedrooms. (2012 IRC R3015)
- Make sure that the bonding device is properly installed on all temporary power poles. (2012 IRC E3609)
- Where rebar is installed in footings, a bonding jumper must be connected from the rebar to the ground in the panel box. (2012 IRC E3608.1.2)
- Tabs in plastic boxes are designed to secure conductors and should not be removed. (2012 IRC E3403.3)
- Outdoor receptacles are required at grade level (not higher than 6’6’’) at the front and back of every dwelling and on every porch and balcony. (2012 IRC E3901.7)
- Observe burial depth requirements for underground cables and raceways (2012 IRC Table E3803.1)
- Nonmetallic cable (Romex) can only be used in dry locations (2012 IRC Table E3801.4) Note: Romex cannot be used in conduit outside to feed a mechanical unit.
- Ground-fault protected outlets are required in the crawl space and basement. (2012 IRC E3902.4 and 3902.5)
No comments:
Post a Comment